  • Interface between the I/O modules and the DCS/PLC
  • Bus coupler for 80 analog or 184 digital channels
  • Communication via PROFIBUS DP
  • HART communication via PROFIBUS DP V1 or service bus
  • Configuration via FDT 1.2 DTM
  • Configuration in run (CiR) for any DCS
  • Non-volatile memory for configuration and parameter settings
  • Self configuration in redundant systems
  • Permanently self-monitoring
  • Outputs drive to safe state in case of failures
  • Installation in Zone 2, Zone 22, Div. 2, or safe area
  • Module can be exchanged under voltage (hot swap)

Datasheet as PDF in following languages:


Technical Data: LB8109*

Supply
Connectionbackplane bus
Rated voltage5 V DC , only in connection with the power supplies LB9***
Power consumption2 W
Fieldbus interface
PROFIBUS DP
Connection9-pin Sub-D socket via backplane
Baud rateup to 1.5 MBit/s
ProtocolPROFIBUS DP/DP V1 read/write services
Number of stations per bus linemax. 125 (PROFIBUS), max. 119 (service bus)
Number of channels per stationmax. 80 analog, max. 184 digital (standard configuration)
Number of stations per bus segmentmax. 31 (RS 485 standard)
Number of repeaters between Master and Slavemax. 3
Supported I/O modulesall LB Remote I/O modules
Configuration (240 bytes I/O)Standard: 80 analog, 184 digital
Universal 2I2O: 48 analog, 184 digital
Universal 4I4O: 60 analog, 120 digital
Bus lengthmax. 1000 m (FOL, 1.5 MBaud),
max. 1000 m (copper cable, 187.5 kBd),
max. 200 m (copper cable, 1.5 MBd)
Addressingvia configuration software
PROFIBUS address0 ... 126
(ex works standard: 126)
GSE fileCGV61710.gsd/gse
HART communicationvia PROFIBUS or service bus
Internal bus
Connectionbackplane bus
Redundancyvia backplane
Indicators/settings
LED indicatorLED 1 (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active
LED 2 (collective alarm): On = internal fault, flashing = no PROFIBUS connection
LED 3 (status process bus): flashing = PROFIBUS receive channel active
LED 4 (status service bus): flashing = service bus receive channel active
LED 5 (operating mode): flashing 1 (1:1 ratio) = active, normal operation; flashing 2 (7:1 ratio) = active, simulation
LED 6 (status process bus): flashing = PROFIBUS response channel active
LED 7 (status servicebus): flashing = service bus response channel active
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1
Conformity
Electromagnetic compatibilityNE 21
Protection degreeIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Shock resistanceshock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100
Vibration resistancefrequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz
Damaging gasfor plugs: 21 days in 25 ppm SO2, at 25 °C and 75 % rel. humidity, device G3
Mechanical specifications
Protection degreeIP20 (module) , mounted on backplane
Connectionvia backplane
Massapprox. 120 g
Dimensions32 x 100 x 103 mm (1.26 x 3.9 x 4 in)
Data for application in connection with Ex-areas
Declaration of conformityPF 08 CERT 1234 X
Group, category, type of protection, temperature classEx-Hexagon II 3 G Ex nA IIC T4
Directive conformity
Directive 94/9/ECEN 60079-0 , EN 60079-15
International approvals
UL approvalE106378
IECEx approvalBVS 09.0037X

Documents: LB8109*

Instructions, Short instructions, Safety informationLanguageFile TypeFile Size
Betriebsanleitung LB8109/Operating instructions LB8109ALLPDF72 KB
Anhang zur Betriebsanleitung: Hinweise zum Einsatz auf See/Annex to Instructions: Application Note for Marine ApplicationsALLPDF89 KB
Manuals
LB Hardware Manual ENGPDF2233 KB
LB-Hardware-HandbuchGERPDF2235 KB
Software Manual for UniCom Bus Coupler 8x09ENGPDF14048 KB
Software-Handbuch für UniCom Buskoppler 8x09GERPDF13857 KB

Approvals+Certificates: LB8109*

CertificatesCertificate No.File TypeFile Size
USA ULE106378 UL (QUZW)LINK---
Canada ULE106378 cUL (QUZW7)LINK---
Europe Pepperl+Fuchs II 3 G Declaration of ConformityPF 08 CERT 1234 XPDF1531 KB
Europe Pepperl+Fuchs 94/9/EC - 2004/108/EC Declaration of ConformityPF 08 CERT 1263PDF370 KB
BVS IECEx Certificate of ConformityIECEx BVS 08.0011XLINK---
DEKRA EXAM IECEx Certificate of ConformityIECEx BVS 09.0037XLINK---
Russia NANIO "CCVE" GOST-RRUSS.IT.GB 05.B03171PDF5562 KB
Bureau Veritas Marine22449/A0 BVPDF81 KB
Det Norske Veritas MarineA-11866PDF1915 KB
American Bureau of Shipping (ABS) Marine10-HG639253-PDAPDF1188 KB
China NEPSI nAc ***GYJ101410XPDF6945 KB

Software: LB8109*

Device Type ManagersRelease InfoFile TypeFile Size
DTM Collection Remote IO/DTM Collection Remote IO7.6.1ZIP47604 KB
Drivers
EDD für Simatic PDM 5.xx und 6.xx/EDD for Simatic PDM 5.xx and 6.xx6.45ZIP550 KB
GSD 1710/GSE 17101.09ZIP8 KB

Associated Products: LB8109*

Predecessor productName
LB8105*PROFIBUS DP/DP V1 Bus Coupler
LB8108*PROFIBUS DP/DP V1 Bus Coupler with Time Stamp Option
AccessoriesName